Analogue Insulation / Continuity Tester STERLING
3132A
- Dust and drip proof construction. (designed to IEC60529
IP54)
- Designed to meet IEC61010-1 and IEC61557 safety standard.
- 1mA rated test current at the minimum resistance.
- 200mA measuring current on continuity testing.
- Automatic discharge of circuit capacitance. (Any charge
stored in the circuit under test will be automatically discharged
after testing.)
- Live circuit warning buzzer and neon lamp.
- Small and lightweight. Shock resistant new case material.
- AC voltmeter with linear, easy-to-read scale.
- Operates on AA, R6P×6 dry batteries
|

|
|
Technical Specification:
|
| Insulation
Resistance |
| Test
Voltage |
250V/500V/1000V |
| Measuring
Ranges (Mid-scale Value) |
100MOhm/200MOhm/400MOhm (1MOhm) (2MOhm)
(4MOhm) |
| Output
Voltage on open circuit |
Rated test voltage+20%, -0% |
| Nominal
Current |
1mA DC min. |
| Output
Short Circuit Current |
1~2mA DC |
| Continuity: |
Range:
0 to 2000 Ohm, low test current for inductive loads |
| Accuracy |
0.1~10MOhm/0.2~20MOhm/0.4~40MOhm
(Accuracy Guaranteed Ranges) ±5% of indicated value |
| Continuity |
| Measuring
Ranges (Mid-scale Value) |
3Ohm/500Ohm (1.5Ohm)/(20Ohm) |
| Output
Voltage on open circuit |
4.1V DC approx. |
| Measuring
Current |
210mA DC min. |
| Accuracy |
|±1.5% of scale length |
| AC
Voltage |
| AC
Voltage |
0~600V AC |
| Accuracy |
|±1.5% of scale length |
| General |
| Safety
Standard |
IEC61010-1 CAT.III 600V Pollution
Degree 2 IEC61010-2-031 IEC61557-1/2/4 |
| IP
Rating |
IEC60529-IP54 |
| EMC
Standard |
IEC61326-1 |
| Withstand
Voltage |
3700V AC for 1 minute |
| Power
Source |
R6P(AA)(1.5V) × 6 |
| Dimensions |
106(L) × 160(W) × 72(D)mm |
| Weight |
560g approx. |
| Accessories |
7122(Test leads) Pouch for test leads
8923(F500mA/600V fuse) × 2 R6P(AA) × 6 Shoulder Strap Instruction
Manual |
Back to the instrument selection
For your price and delivery inquires, application
details comments, and general feedback, please select Feedback Mailbox
Last updated: April 04, 2007
|