KYORITSU 4202A Earth Clamp Tester – Duncan Instruments Canada Ltd
KYORITSU 4202 Earth Clamp Tester
KYORITSU 4202 Earth Clamp Tester
KYORITSU 4202 Earth Clamp Tester

KYORITSU 4202A Earth Clamp Tester

Regular price $ 1,956.00 CAD $ 1,495.00 CAD Sale

Real time measurements can be transferred, shown and saved on Android device (up to 100 measurements). Saved data includes measurement, GPS location and date & time.

Comparator function on Android device informs when the measured value is lower/higher than the preset value

Earth /Ground resistance and Leakage current measurement functions
• The earth resistance from 0.05 to 1500 Ω can be measured without the auxiliary earth spikes in multi-earthing systems
• True RMS leakage or phase current readings from 0.1mA to 30.0A provides vital additional information in earthing networks
• Filter function offers increased immunity to electrical noise and a Noise mark appears in excessively high noisy environments

Specification

Earth resistance Auto range 20.00/200.00/1500Ω
±1.5%±0.05Ω(0.00 - 20.99Ω) 
±2%±0.5Ω(16.0 - 99.9Ω)
±3%±2Ω(100.0 - 209.9Ω) 
±5%±5Ω(160 - 399Ω)
±10%±10Ω(400 - 599Ω)
AC current (50Hz/60Hz) Auto range Values are displayed, but accuracy isn't guaranted(600 - 1580Ω)
100.0/1000mA/10.00/30.0A
±2%±0.7mA(0.0 - 104.9mA)
±2%(80mA - 31.5A)
Operating indication Earth resistance function :
Constant voltage injection
Current detection (Frequency : Approx.2400Hz)
Dual Integration
AC current function : Successive approximation
Over-range indication "OL"is displayed when input exceeds the upper limit of a measuring range
Response time Approx. 7 seconds (Earth resistance)
Approx. 2 seconds (AC current)
Sample rate Approx. 1 times per second
Communication Interface Bluetooth Ver2.1 + EDR Class2
Current consumption Approx. 50mA (max.100mA)
Measurement time Approx.5 hours (when R6 is used) Approx. 21 hours (when LR6 is used)
Auto power-off Turns power off about 10 minutes after the last button operation.
Conductor size Approx.Ø32mm
Applicable standards IEC 61010-1 CAT Ⅳ 300V Pollution degree2
IEC 61010-2-032, IEC 61326 (EMC)
Power source DC6V : R6(sizeAA manganese battery) x 4
or LR6 (sizeAA alkaline battery) x 4
Dimensions 246(L)×120(W)×54(D)mm
Weight Approx. 780g (including batteries)
Included Accessories LR6 x 4, Instruction manual
8304 (Resister for operation check)
9167 (Carrying case[Hard])

Download

Compare to