Two input channel logger capable of recording True RMS current (compatible with AC current probes with voltage outputs) and True RMS voltage to 600V. Stores up to 240,000 measurements.

The AEMC L562 Simple Logger II is a two channel Volt/Amp data logger. The Extended Recording Mode (XRM) and delayed start time are just two of the many application friendly features.

The Simple Logger® II records TRMS at a rate of up to eight times per second. The measurement process is performed no more than eight times per second. TRMS calculations are performed on a single line cycle. This means that the input(s) are ignored between measurement intervals.

The main advantage of the logger is its ability to perform a variety of recording tasks with easy and intuitive setup from a computer using DataView® software.

Analog information on the input is sampled and converted to a digital signal. This digital signal is processed and stored along with scale and time information. An optically isolated Universal Serial Bus (USB) port provides for the transfer of data from the instrument’s internal memory to the computer for analysis.

Probes are not included and must be purchased separately:

Also available as a kit with probes:

Features

  • 2 input channels
  • Voltage: 0 to 600VAC TRMS
  • Current: compatible with voltage output AC current probes with voltage outputs
  • 64 samples per cycle
  • Records Arms, Vrms & VA (VA displays in DataView® software)
  • 4 user selectable storage modes
  • Programmable storage rates from 8 every second to 1 every day
  • Stores up to 240,000 measurements in non-volatile memory
  • Powered by standard Alkaline batteries
  • Lightweight, compact, fits anywhere
  • 5 LED indicators quickly and clearly display logger status
  • Includes FREE DataView® software for data storage, real-time display, analysis and report generation
  • EN 61010-1; 300V CAT IV; 600V CAT III with a safety rated current probe attached
  • Isolated USB 2.0 communication cable included

Applications

  • Single phase power monitoring
  • Residential, commercial, industrial troubleshooting
  • Find sags and surges
  • Track energy usage

Specifications

Current Channel
Input Connection BNC
Input Range 0 to 1V AC (for use with current probes with a voltage output)
Resolution 0.1mV
Accuracy (50/60Hz) 0 to 10mV unspecified
10 to 50mV: ±(0.5% of Reading + 1mV)
50 to 1000mV: ±(0.5% of Reading + 0.5mV)
Input Impedance 800kΩ
Maximum Input Voltage 5Vrms or ± 7.07V peak
Voltage Channel
Input Connection Two recessed banana jacks
Input Range 0 to 600V AC
Resolution 0.1V
Accuracy (50/60Hz) 0 to 5V unspecified
5 to 50V: ±(0.5% of Reading + 1V)
50 to 600V: ±(0.5% of Reading + 0.5V)
Input Impedance 40MΩ
Maximum Input Voltage 1.2 x 600V
Electrical  
Sample Rate 64 samples/cycle
Storage Rate Programmable from 8 every second to 1 every day
Storage Modes Start/Stop, FIFO, Extended Recording Mode (XRM™) and Alarm
Recording Length 15 minutes to 8 weeks, programmable using DataView®
Memory 240,000 measurement (512KB)
Data is stored in non-volatile memory and retained if the battery is low or removed
Communication USB 2.0 optically isolated
Power Source 2 x 1.5V AA-cell Alkaline batteries (included)
Battery Life 100 hours to > 45 days (dependent on sample rate and recording length)